What is the pre-installation procedure for revenue meter PM8000 ?
End user needs to revenue lock an PM8000 series meter and needs to what prerequisites are required to place the meter in the revenue lock state
Product:
PM8000 Series Meter
Environment:
Power Metering
Resolution:
You must configure and revenue lock your meter before installation.
• Clear all meter data prior to installing your revenue meter.
• Unlock your revenue meter.
• Configure the required revenue settings specific for installation. Once the meter
is locked, these settings cannot be changed.
• Verify the revenue settings have been implemented.
• Revenue lock your meter.
• Verify the meter is revenue-locked.
• Install the meter according to your meter’s install sheet.
• Install the voltage and current terminal covers according to the sealing kit
installation instructions.
For Instructions on how to revenue lock your PM8000 please check out FA317280