How to troubleshoot an ILF fault on an Altivar Process Drive?
Issue:
What is the cause of  ILF [Internal Link Error] fault on an Altivar Process Drive?

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
N/A

Resolution:

Cause
Communication interruption between option module and the drive.

Remedy
  • Verify connection to the proper slot
    • Slot A
      • Communication Modules (DeviceNet, Ethernet IP, Profibus, ProfiNet...)
      • I/O & Relay Module
    • Slot B
      • Encoder Card (Analog, Digital, Resolver...)
      • I/O & Relay Module
  • Verify the environment (electromagnetic compatibility)
  • If using Communication Module, check drives firmware version. (For most cases it should be at least V1.5IExx)
  • Save configuration file on keypad, remove option module and do a factory reset. If fault disappears then it might be a bad option module.
  • Replace the option module.

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings