Issue:
ATV12 drive capability to run a motor up to 400Hz
Product Line:
Altivar 12, ATV12
Environment:
All
Cause:
Wants to run the motor up to 400hz
Resolution:
Programming the drive
DRC menu
bFr=60hz
UNS = motor voltage
Ncr motor current
FRS= 400hz
tFr =400hz
Main menu
ACC=3 seconds suggested 10 seconds
DEC 3 seconds
LSP 0 (for a test, set 400hz if you do not have a voltage or current feedback speed input)
HSP 400hz
ATV12 drive capability to run a motor up to 400Hz
Product Line:
Altivar 12, ATV12
Environment:
All
Cause:
Wants to run the motor up to 400hz
Resolution:
Programming the drive
DRC menu
bFr=60hz
UNS = motor voltage
Ncr motor current
FRS= 400hz
tFr =400hz
Main menu
ACC=3 seconds suggested 10 seconds
DEC 3 seconds
LSP 0 (for a test, set 400hz if you do not have a voltage or current feedback speed input)
HSP 400hz