Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
		
En quoi pouvons-nous vous aider aujourd'hui ?
How to make the PWD_DIAG and PWD_CMD work upon M580 HSBY swap
Question:
By default, customer found the function blocks PWD_DIAG and PWD_CMD for BMX CPS 4022 were not working properly upon M580 HSBY swap.
How to make the PWD_DIAG and PWD_CMD work upon M580 HSBY swap?

Answer:
It’s the known restriction for M580 HSBY that during a Switchover event, asynchronous communication function blocs which use internal management parameters do not automatically resume operation on the new Primary PLC without special care.

Program your application so that all EFBs instances are not exchanged with Standby PLC. To do this, de-select the Exchange on STBY attribute for the EFB instance

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings