{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
Consulter notre FAQ
Enclosed ATS22 soft starter is not running in Auto mode.

Article available in these languages: Espagnol

Issue:
ATS22 Not Running in Auto Mode.

Product Line:
8639 22U enclosed ATS22

Environment:
All

Cause:
Auto start is not starting the soft starter.

Resolution:
Normally the auto start for auto is terminals 5-6.  So the end customer will need to close a set of dry contacts on these terminals to start the unit in Auto mode.

You can find the basic wiring diagrams in the Enclosed Altistart 22 manual
https://www.se.com/us/en/download/document/30072-453-26/

Schneider Electric Belgium

En savoir plus
Gamme :
Articles utiles
En savoir plus
Gamme :