Issue:
Protection against phase inversion with ATS48.
Product Line:
Altistart 48, ATS48
Environment:
All models
Cause:
NA
Resolution:
The ATS48 does have a phase inversion protection feature, but it needs to be activated. In the PrO menu, set PHr = 123 or 321 to match the required rotation. If the rotation does not match, the ATS48 will fault with PIF code.