Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
		
En quoi pouvons-nous vous aider aujourd'hui ?
What is the scaling of PID feedback value when the feedback is taken from pulse input on LI5?
The scaling between feedback value (RPF parameter) and the pulse input when assigned as PID feedback (PIF=RP) dependss on following parameters:
- min PID feedback setting (PIF1)
- max PID feedback setting (PIF2)
- min pulse input frequency (PIL)
- max pulse input frequency (PFR)
The conversion between pulse input value and PID feedback is linear and PIL corresponds to PIF1 and PFR corresponds to PIF2.

For example, PIL=5kHz, PFR=20kHz, PIF1=0, PIF2=10000
Then
- at input frequency below 5kHz, the RPF=0
- at input frequency 10kHz, the RPF=3333
- at input frequency 15kHz, the RPF=6666
- at input frequency 20kHz, the RPF=10000

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings