What are the minimum currents to detect a fault?
Example for Over-current (DT curves) :
  • Minimum threshold for detecting phase-to-phase faults: 0.02 In-4 In
  • Minimum threshold for detecting zero sequence Faults : 0.008 In-1.6 In