Graphic Display terminal VW3A1111 of Altivar Variable speed drives (ATV6xx/ATV9xx) used for RESET function

The VW3A1111 Graphic Display Terminal can be used to perform a drive RESET on Altivar ATV6xx / ATV9xx drives, regardless of the configured control channel.
However, this functionality must be explicitly enabled in the drive parameters.

Parameter setting
Navigate to:
5.5 Command and Reference → Stop key Enable (PST parameter)

Default value: Yes
Available values:

No
Yes
All


Key configuration

When set to All, the drive reset function via the VW3A1111 terminal is enabled for all control channels
This allows the reset to be executed independently of the active control mode (e.g. terminals, fieldbus, HMI)


Practical implication

Without selecting All, the reset command may be restricted by the active control channel
For maintenance and troubleshooting, setting All ensures that the HMI reset is always available

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings