What can trigger a bUF or braking unit resistor short circuit fault on the ATV930 Process drives?
Getting a bUF or braking unit resistor short circuit fault on the ATV930 Process drives.
Product Line:
Altivar Machines, Altivar 930
Cause:
Short circuit inside the braking module
Braking resistor is shorted out
Short circuit to ground
BRA=No ( ramp auto adaptation) and no DB resistor
Resolution:
Check the braking units wiring and the resistor connections
Check the drives configurations
NOTE: ATV630 drives do not accept DB resistor connections.