Question:
How to coordinate the start address of IOscanner at BMENOC0301 of M580 system to communicate with Quantum?
Answer:
Inside IO scan configurator of M580 system, the RD Address/WR Address is referring to address of counterpart.
Since M580 starts from %MW0 while Quantum start from %MW1, you have to assign the address 99 at M580 IOscan configurator to correspond to the address 100 at Quantum.
How to coordinate the start address of IOscanner at BMENOC0301 of M580 system to communicate with Quantum?
Answer:
Inside IO scan configurator of M580 system, the RD Address/WR Address is referring to address of counterpart.
Since M580 starts from %MW0 while Quantum start from %MW1, you have to assign the address 99 at M580 IOscan configurator to correspond to the address 100 at Quantum.