How many wires can you install on the Power poles for the LC1D65A contactor?
Issue:
Quantity of wires installed on the Power poles for the LC1D65A contactor.

Product line:
Tesys D, Everlink

Environment:
LC1D40A LC1D50A LC1D65A

Resolution:
The LC1D40A to LC1D65A Everlink version contactors can use 2 power cables per phase.  1x AWG 16 to AWG 4 plus 1x AWG 16 to AWG 2.

Instruction bulletin attached.

Schneider Electric Belgium

Pièce(s) jointe(s)
1727189_01a55.pdf [18.77 MB]