{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
Consulter notre FAQ
Getting premature schedule manufacturer maintenance alarm on Masterpact MTZ Micrologic X control unit
Issue:
Why am I getting a scheduled maintenance alarm when  the breaker is brand new and recently placed into service?
Sched. Manufact. maintenance within 3 months  Id: 0x1482

Product Line: Circuit Breakers

Environment: Masterpact MTZ with Micrologic X  control unit

Resolution:
The commissioning date within the control unit may have been left blank.  Use EcoStruxure Power Commision (EPC) commissioning software to correctly fill in the commissioning date.  See attached screen shot, to locate commissioning date in EPC.

Schneider Electric Belgium

Pièce(s) jointe(s)
Commissioning Date in EPC.jpg [27.21 KB]
MTZ Schedule manufacturer maintenance within 3 months on display Id 0x1482.JPG.jpg [61.76 KB]
En savoir plus
Gamme :
Articles utiles
En savoir plus
Gamme :