Why does the Com’X Return Modbus Exception 0x0a When Polling the Digital Inputs?
The environment for this FAQ includes one or more remote Modbus TCP/IP clients such as PME, PSO, or third party application polling the Com’X digital inputs.
Issue
The Com’X periodically returns “Gateway Path Unavailable (0x0a)” exceptions when polling its analog or digital inputs. This happens at the top of each hour and continues for up to 20 seconds. This behavior can cause nuisance alarms and comms failures if the client is not configured to manage the exception.
Root CauseThere is a 10-20 window at the top of each hour where communication to the Com’X Inputs can be delayed due to blocking background applications. The Com’X returns the GATEWAY PATH UNAVAILABLE (0x0a) exception indicating the inability to access the inputs.
Prevention
There is no way to prevent this behavior.
Detection
The issue can be detected by the reply of exception 0x0a when polling the Com’X inputs.
Resolution
- Remote applications polling the Com’X inputs must be configured to tolerate this behavior by the implementation of retry logic.
- The combination of retries and time between retries should be configured to span the 20 second period where application is busy, and exceptions are returned.
Publié pour: Schneider Electric Belgium


Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.