Why is the MOD_FLT of x80 DI/DO modules different between the local rack and the EIO rack?

In an M580 application, the device DDT associated with an X80 DI/DO module includes the MOD_FLT word.

For modules installed in an Ethernet RIO rack, background exchanges between the M580 CPU and the BMxCRA312x0 adapter update the device DDT.

The MOD_FLT information is not available for modules installed in the M580 local rack, including when using the READ_STS_MX EFB. This limitation is related to the M580 architecture.

To retrieve MOD_FLT for a module in an Ethernet RIO rack:

1- Enable Allow dynamic arrays (ANY_ARRAY_XXX) in EcoStruxure Control Expert:

  • For M580 Safety: Tools > Project Settings > Scope: Process > Variables
  • Standard M580: Tools > Project Settings > Variables

2- Create a section using the READ_STS_MX and ADDMX EFBs

3- Configure ADDMX with the IP address of the corresponding BMxCRA312x0 adapter

img1

For more information, see page 306 of the "Modicon X80 Discrete Input/Output Modules User Manual".

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Conditions générales d'affaires
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings
  • Centre de Préférences