Why is my M580 stopped after a loss of power?

Issue
PLC is stopped after loss of power

Product Line
M580

Environment
EcoStruxure Control Expert

Resolution
The CPU will only go back into run if you have Automatic start in Run checked off in the configuration. Otherwise it will be stopped when power is restored.