Issue
In one of our installed MICOM P343 relay, Generator low impedance differential protection is enabled and protection is working fine however the differential & bias current measurement is not showing up in MEASUREMENT 3 folder. As per manual it should be available in Measurement 3 folder.
_____________________________________________________________
Product Line
MiCOM P343 Firmware version 35
_____________________________________________________________
Environment
Parameter "System config" [09.0B] value is set as invisible.
_____________________________________________________________
Solution
Issue can be resolved by either making visible the "System config" parameter or by upgrading the device to FW version 36. There is no harm in keeping the "System config" as invisible.

To upgrade the device please reach to local SE contact.
_____________________________________________________________
*Warning: Installation, maintenance, up-gradation, down-gradation of MiCOM device should only be performed by qualified, competent personnel that have appropriate training and experience. Failure to follow the instructions / warnings in the Installation / Operation Guide can result in unwanted disruption to the power system, permanent damage to the device, severe injury or death.*
In one of our installed MICOM P343 relay, Generator low impedance differential protection is enabled and protection is working fine however the differential & bias current measurement is not showing up in MEASUREMENT 3 folder. As per manual it should be available in Measurement 3 folder.
_____________________________________________________________
Product Line
MiCOM P343 Firmware version 35
_____________________________________________________________
Environment
Parameter "System config" [09.0B] value is set as invisible.
_____________________________________________________________
Solution
Issue can be resolved by either making visible the "System config" parameter or by upgrading the device to FW version 36. There is no harm in keeping the "System config" as invisible.
To upgrade the device please reach to local SE contact.
_____________________________________________________________
*Warning: Installation, maintenance, up-gradation, down-gradation of MiCOM device should only be performed by qualified, competent personnel that have appropriate training and experience. Failure to follow the instructions / warnings in the Installation / Operation Guide can result in unwanted disruption to the power system, permanent damage to the device, severe injury or death.*
Publié pour: Schneider Electric Belgium


Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.