What does the diagnosis LED ON mean on TeSys Giga contactors ? How many on/off operations left after the LED is ON ?
The diagnostic LED shall be ON,
  1. when the contactor (switching module) reaches its end of life, means it have reached 85% of its electrical life. The electrical life depends on the operational voltage and current, utilisation category, make break current (AC3/AC3e) and depends on application type. So, the remaining number of operations shall also vary depending on multiple factors : 1 beat
  2. Coil undervoltage (A1-A2 <0.8Uc): 2 beats
  3. Coil overvoltage (A1-A2 )1.1Uc): 3 beats
  4. Internal fault: continuous beats
  5. Remote wear diagnosis (RWD) module (only when Advanced version) cannot enable remote alarm for central monitoring: 4 beats
Note that detail information refers to installation guide DOCA0189EN and here is the link: TeSys Giga Series - Contactors and Electronic Overload Relays - Installation Guide User guide | Schneider Electric

Schneider Electric Belgium

  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings