What is a E18 fault on my ATV212 drive?

Issue:

Customer is getting a E18 fault on his ATV212 drive

Product Line:

ATV212

Environment:

E18

Cause:

n/a

Resolution:

E18 fault is a loss of the VIA analog input signal, below the level that is set by Parameter F633. F633 can be set to 0 (disabled) or 1-100 (Fault detection Level).