PME 2021 - KPI Report not saving the calculated data into the database
Product Line
Power Monitoring Expert 2021 - CU 1
_____________________________________________________________
Environment
Web Application - Reports
_____________________________________________________________
Issue
KPI Report not saving the calculated data into the database.
The following error message is logged into ION_Systemlog:
KPI Calculation Engine Failed. See system logs for details
"Could not load file or assembly 'MeasurementManager.Data, Version=1.0.0.0, Culture=neutral, PublicKeyToken=null' or one of its dependencies. The system cannot find the file specified."
_____________________________________________________________
Root Cause
The MeasurementManager.Data.dll file was missing from the system\ReportDataService\bin\
_____________________________________________________________
Proposed Solution
Make a copy of the MeasurementManager.Data.dll file located at system\bin and place it in the system\ReportDataService\bin folder