undefined undefined
{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
En quoi pouvons-nous vous aider aujourd'hui ?
In Ecostruxure Operator Terminal Expert 3.2 SP1 how many devices can be added using a Modbus TCP driver?

Issue:

How many devices can be added on Ecostruxure Operator Terminal Expert 3.2 SP1 when using a Modbus TCP driver?

Product Line:

Ecostruxure Operator Terminal Expert 3.2 SP1, HMIST6, HMISTM6, HMIG3U, HMIG5U22, HMISTO735 and iPC.

Resolution:

The maximum number of devices that can be added under the Modbus TCP driver depends on the HMI model, as follows:

HMIST6 family: Up to 32 devices.

HMISTM6 family: Up to 32 devices.

HMIG3U/HMIG5U22: Up to 64 devices.

HMISTO735: Up to 16 devices.

iPC: Up to 64 devices.