{}

Nos marques

Bienvenue sur le site Web de Schneider Electric

Bienvenue sur notre site Web.
Consulter notre FAQ
How to Read Smartlink Embedded Configuration Registers
Issue:
I got a "Slave Device Failure" Modbus exception when I read the Embedded Configuration Registers for a Smartlink device.

Resolution:
Embedded Configuration Registers for a Smartlink must by read with a block of 64 Registers

Example:
  • for Channel_1 - Input 1 => you need to poll 64 registers from Register 20010
  • for Channel_1 - Input 2 => you need to poll 64 registers from Register 20074
  • for Channel_7 - Input 2 => you need to poll 64 registers from Register 20778

Schneider Electric Belgium

En savoir plus
Produit :
En savoir plus
Produit :