How is ramp switching set up on the ATV900 series Process drive?
Issue:
ATV900 ramp switching set up.
Product Line:
Altivar 930 and 950
Environment:
All
Cause:
Dual ramp rates
Resolution:
Under the Main menu, select Complete settings menu.
Select the Generic functions menu and then Ramp switching
There are 2 ways of doing ramp switching from the typical ACC/DEC settings:
Using frequency threshold
Ramp 2 thd (FRT) assigns an output frequency above which the AC2/DE2 apply. Note that ACC/DEC apply when below the frequency threshold.
Using a logic input to switch ramp
Ramp Switch Assign (RPS) assigns a logic input to activate the second ramp, AC2/DE2.