Control Expert v15 Takes a Long Time to Start Without Internet Connection

Issue:
When launching Control Expert v15.0 SP1, the application takes approximately 5 to 7 minutes to start if there is no internet connection, but only a few seconds when connected to the internet.

Product line:
Control Expert v15.0 SP1

Environnement:
Windows

Resolution:

  1. Press Windows + R, type gpedit.msc, and press Enter to open the Local Group Policy Editor.
  2. Navigate to:
    Computer ConfigurationWindows SettingsSecurity SettingsPublic Key PoliciesCertificate Path Validation Settings
  3. In the Network Retrieval tab:
    • Check "Define these policy settings"
    • Set:
      • Default URL retrieval timeout to 1 (instead of 15)
      • Default path validation cumulative retrieval timeout to 2 (instead of 20)

Certificate Path Validation Settings Properties

4. Apply the changes and restart the system if necessary.

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings