How to enable the datalogging service of a BMENOR2200H RTU module?

Issue:
How to enable the datalogging feature on the BMENOR2200 RTU module and make It available on its webpage.

Product Line:

BMENOR2200H RTU module

Environment:

  • EcoStruxure Control Expert V15.0 with “ControlExpert_V150_HF_Integrity_check” and “ ControlExpert_V150_HF_BMENOR2200H” installed, or EcoStruxure Control Expert V16.0 & later.
  • BMENOR2200H SV3.01.07 firmware & above.

Resolution:

The datalogging service becomes available on the BMENOR2200H RTU module since its firmware version SV3.01.07 and later , using EcoStruxure Control Expert V15.0 and above:

BMENOR2200H firmware history
To make the datalogging service available, It is mandatory to select the BMENOR2200.2 or BMENOR2200.3 in the hardware configuration of the project:

Hardware catalog

The datalogging will be then available on the DTM of the BMENOR2200H:

DTM screenshot

And also accessible from its webpage:

webpage screenshot

Webpage screenshot 2