Issue
The Power Quality Performance Module is not updating.  Event logs do not update. Status objects on diagram do not reflect changes. 
Product Line
Power Quality Performance Module 
 
Environment
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Cause
- There has been a recent change to the certificate binding, restricting the HTTP port and enabling the HTTPS port.
- The local server address in the SQL server database has been hardcoded.
Resolution
Before continuing, confirm that VIP.PQADVISOR has been correctly configured. 
Resolution 1:
- Verify that all steps were taken in FA309041  to restrict HTTP port access and enable HTTPS access. Particularly, check that the web config file has been properly commented to reflect changes. - 
 
- 
- Verify that the ION_Network and Application_Modules database has been reconfigured so that the local server address reflects the proper domain name. - Example: 
 
- Example: 
- Confirm that HTTPS binding has been deleted from the site bindings.
- Confirm host is pointing to the correct domain name.
Resolution 2
- Open Designer. Navigate to VIP.PQADVISOR. 
- Confirm that each XML Import Module reflects the correct URL address. 
- Reinitialize the diagrams. 
Publié pour: Schneider Electric Belgium
Besoin d'aide ?
- Sélectionnez le bon produit- Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications. 
- Obtenir un devis- Effectuez une demande de renseignements en ligne et un expert vous contactera. 
- Où acheter ?- Trouvez facilement le distributeur Schneider Electric local le plus proche. 
- Centre d'aide- Trouvez des ressources de support pour tous vos besoins, en un seul endroit.