How to upgrade your NMC2 & NMC3 firmware using the NMC Firmware Update Utility

Article available in these languages: Français

Issue:
The customer asked how to upgrade the firmware through the utility tool.

Product line:
NMC2, NMC3

Environment:
AP9630, AP9631, AP9640 & AP9641

Cause:
Web interface displays a UPS "not recognized" error or the customer is installing a new NMC.

Resolution:
Please follow the next steps.
1. Access the Downloads page.

2. Locate firmware for the product by NMC model (ie AP9630).

(NOTE: Some products' firmware is not available on the download page. Contact Technical Support for support on products not found on the firmware download page.)

3. Run the application and enter the following information.

  1. Host (Ip address of the unit)
  2. UserName and Password of the NMC
  3. Click on Start Update

If you notice that the application stops with the selected protocol (SCP for this case) please try with FTP.
Firmware utility



Schneider Electric Belgium

  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings