Factory reset of M580 CPU with Engineering Link set to "Enforced"

Issue:


Unable to connect to M580 because the password was forgotten and the Engineering Link mode was set to "Enforced".


When Engineering Link is set to Enforced, you are forced to create an application password. Also the only protocols that can now be used to connect are:


HTTPS

HTTPS via USB


when using those protocols, you can no longer use the SHIFT + F2 method to obtain a code that will allow engineering to provide a recovery password if you forget the application password.


Also the method of moving the CPU one slot over to the right does not work in this mode.


We are left with no method of clearing the CPU back to NO CONF mode.


Products:


M580 CPU with firmware 4.20 and up

Control Expert 16.0 and up


Resolution:


There are 2 methods that can allow us to recover the CPU with an "Enforced" engineering link.


Method 1 : This method will require you to know the password for the firmware update.


Using EcoStruxure Automation Device Maintenance, you can downgrade the CPU back to firmware 3.20. Since this version did not support the Engineering link feature, the CPU will reject and erase the application when downgrading.


You will need a special firmware in order to downgrade your 4.20 and up back to 3.20. Please contact your Schneider technical support group to get that firmware. This is required in order to check if your M580 CPU Product version (PV) allows for a downgrade back to 3.20



Method 2 : This will require an M580 SD card (BMXRMS004GPF) and a spare M580 CPU of the same model


In the spare CPU, create an application with no application password. The engineering link mode might have to be set to "Full Access". Make sure to insert the SD card in the CPU before transferring this application in the spare CPU.


Once this is done, power down the spare CPU and retrieve the SD card.


Power down the "locked" CPU and insert the SD card.


Power the CPU back up. The program in the SD card will overwrite the one in the CPU, effectively replacing the application with the "Enforced" option.



Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :

Besoin d'aide ?

  • Sélectionnez le bon produit

    Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.

  • Obtenir un devis

    Effectuez une demande de renseignements en ligne et un expert vous contactera.

  • Où acheter ?

    Trouvez facilement le distributeur Schneider Electric local le plus proche.

  • Centre d'aide

    Trouvez des ressources de support pour tous vos besoins, en un seul endroit.

  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings