PME - excessive "Site connected" messages in the system log

Issue

The PME system log is filled with repeating "Site connected" messages, making it difficult to navigate and maintain the system log.

Site connected messages

Product Line

Power Monitoring Expert 7.x
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024

Environment

System Log Events


Cause

Some Modbus TCP devices quickly close idle connections resulting in PME frequently establishing a new connection with the device.


Resolution

Use the VIP to frequently poll a register to serve as a "keep-alive" so the device doesn't close the connection.

1. Review the "Site connected" messages in the system log and take note of each unique site and/or device mentioned, in this example it's occurring with 2 sites "Sub6_XMFRS" and "Sub7_XMFRS":

Identify devices or sites with Site connected messages

2. Open and log into Designer.

3. Go to File > Open and select a VIP, this example will use VIP.DEFAULT:

Open a VIP

4. Click and drag an Arithmetic Module onto the diagram:

Create Arithmetic Module

5. Click on the small blue input circle on the Arithmetic Module then select "NEW Source":

Select NEW Source

6. With the dotted line following your mouse, click on the ION button on the top toolbar:

Click ION button to link

7. Link to a register either on a device or a device under a site that has recurring "Site connected" messages. In this example it's a site so the link will be to a serial device added to the site:

Link to register on device or device under a site with Site connected messages

8. File > Save the VIP, then do shift+left-click on the input circle of the Arithmetic Module to confirm a value is displayed. Note: if linking a serial device under a site and "n/a" is displayed instead of a value, try linking a different serial device that is communicating. If the linked register is not displaying a value, it won't prevent the "Site connected" messages.

Confirm linked register shows value

9. Repeat for remaining devices and/or sites that have recurring "Site connected" messages.

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :

Besoin d'aide ?

Besoin d'aide ?

Sélectionnez le bon produit

Sélectionnez le bon produit

Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.

Obtenir un devis

Obtenir un devis

Effectuez une demande de renseignements en ligne et un expert vous contactera.

Où acheter ?

Où acheter ?

Trouvez facilement le distributeur Schneider Electric local le plus proche.

Centre d'aide

Centre d'aide

Trouvez des ressources de support pour tous vos besoins, en un seul endroit.

  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings