Adjusting Overload Threshold Settings on Galaxy VS

Issue:

Customers would like to adjust the overload threshold setting to reduce frequent warning alarms on Galaxy VS.

Product Line:

Galaxy VS

Environment:

Galaxy VS (All versions)

Cause:

The default overload warning threshold is set to 75%, which may generate frequent alarms depending on the load profile.

Alarms:

Load on UPS in below warning level

Load on UPS is above warning level

Resolution:

The overload threshold can be adjusted directly from the UPS display. Follow these steps:

  1. Be physically in front of the unit.
  2. Navigate to:
    Configuration → Output
  3. If prompted for login credentials, use:
    • Username: admin
    • Password: admin (all lowercase)
  4. Modify the Overload Threshold % setting as required (e.g., increase to 90% to reduce alarms).

Overload threshold menu

Schneider Electric Belgium

En savoir plus
Gamme :
En savoir plus
Gamme :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings