How to update SCADAPack x70 RTU BOOTLOADER using PuTTY or Windows Command Prompt
Step 1: Transfer the Bootloader File to the RTU
- Open RemoteConnect and connect to the SCADAPack 47x RTU via USB.
- Enable the Telnet Service on the device.
- Go Online with the device and write the project to the SCADAPack 47x RTU.
- Right-click on SCADAPack x70 Controller Settings – DeviceDTM, then go to:
- Additional Functions > Write File to Device
- In the Write File to Device window:
- Click Browse, locate the bootloader file (e.g., SP47x_BL_151.blz), and click OK.
- Wait for the file transfer to complete.
-
Step 2: Apply the Firmware Patch Using PuTTY
- Open PuTTY and connect to the RTU using the USB IP address:
10.2.3.4. - Type the command: DIR
- This verifies that the bootloader file exists on the device.
- Type the command: RESTART BOOTMON *.blz
- Example:
- RESTART BOOTMON SP47x_BL_151.blz
- Open PuTTY and connect to the RTU using the USB IP address:
- Wait for the firmware patch to complete. The PuTTY session will disconnect automatically.
- Reconnect using PuTTY and type: VER
- This displays the updated bootloader version.
-
Step 3: Apply the Firmware Patch Using Windows Command Prompt
- Open Windows Command Prompt and type: Telnet 10.2.3.4
- This will connect to the SCADAPack x70 RTU.
Type the command: DIR
- This verifies that the firmware file is present.
Type the command: RESTART BOOTMON SP47x_BL_151.blz
- Wait for the patch to complete. The connection will be lost.
- Reconnect using command: Telnet 10.2.3.4
- Type the command: VER
- This displays the updated firmware version.
Publié pour: Schneider Electric Belgium
Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.