En quoi pouvons-nous vous aider aujourd'hui ?
RemoteConnect Logic Status Code: -8463 (16#DEF1) Character String Transfer Alert.
What is a Character String Transfer Alert?
A Character String Transfer Alert occurs when a string operation attempts to:
- Transfer more characters than the destination string can hold.
- Copy data into a string that exceeds the maximum configured length.
- Concatenate multiple strings and exceed the destination string capacity.
- Receive malformed string data from an external device
How to diagnose in Logic Editor (Control Expert).
- Go to Mode menu and then connect to the device.
- Go to Tools menu and select Diagnostic Viewer
Examine the Diagnostic Viewer window and it will provide the location of the error in the program.
In this example program, the variable "Result_String" was set to default 16 characters limit which was causing the issue.
Assigned Variables:
Program:
To correct the issue, increase the variable "Result_String" to have a 32 character limit by changing the Type to String[32]
Summary
The RemoteConnect String Overflow Error corresponds to Control Expert's Character String Transfer Alert (-8463 / 16#DEF1). The alert occurs when a string operation attempts to move, copy, or build a string larger than the available destination size. To diagnose the issue, monitor %S15, inspect string handling logic, review communication data received from RemoteConnect, and verify that all PLC string variables are sized appropriately.
Publié pour: Schneider Electric Belgium
En savoir plus
Gamme :
En savoir plus
Gamme :
Besoin d'aide ?
Sélectionnez le bon produit
Trouvez rapidement et facilement les produits et accessoires adaptés à vos applications.
Obtenir un devis
Effectuez une demande de renseignements en ligne et un expert vous contactera.
Où acheter ?
Trouvez facilement le distributeur Schneider Electric local le plus proche.
Centre d'aide
Trouvez des ressources de support pour tous vos besoins, en un seul endroit.