Why my BMENUA0100 is not NTP synchronized in “CA only” or “Selfsign & CA” mode?

With BMENUA0100 FW 3.01.34, it is important to synchronize the module with an NTP server before changing the PKI mode.

After a Factory Reset, the BMENUA0100 starts in “Self-Signed only” mode.

1

Before switching to “CA only” or “Selfsign & CA”:

  • Check that the NTP Client Service to “ON”.
  • Wait until the BMENUA0100 is correctly synchronized.
  • Check that the date and time displayed on the Home page are correct.

1

  • Change the PKI mode to “CA only” or “Selfsign & CA”.

3

The BMENUA0100 will then restart with the NTP Client Service set to “OFF”, while retaining the correct date and time.

4

An incorrect module time may cause problems when importing a CA-signed certificate.

Once the CA-signed certificate is imported and new configuration applied to the BMENUA0100 module, the NTP client Service will be set to "ON"

Schneider Electric Belgium

En savoir plus
Produit :
En savoir plus
Produit :
  • Documentation produits
  • Téléchargement de logiciels
  • Sélecteur de produits
  • Substitution et remplacement de produits
  • Centre d'aide et de contact
  • Trouver nos sites
  • Obtenir un devis
  • Où acheter
  • Communauté Schneider Electric
  • Carrières
  • Qui sommes-nous ?
  • Signaler une mauvaise conduite
  • Accessibilité
  • Salle de presse
  • Partenaires
  • EcoStruxure
  • Nos emplois
  • Blog
  • Soyez informé des nouveautés en premier ?
  • Conditions générales d'affaires
  • Protection des données
  • Mention sur les cookies
  • Conditions d utilisation
  • Conditions générales de vente et d'achat
  • Change your cookie settings
  • Centre de Préférences