Is it possible to monitor the Primary and Standby PLC state of the M580 redundant system via the Ecostruxure OPCUA Server Expert?
Issue:
Monitoring the Primary and Standby PLC state of the M580 HSBY system via the Ecostruxure OPCUA Server Expert 2.1.4906 SP3
Product Line:
Ecostruxure OPCUA Server Expert
Resolution:
Yes, it is possible via the "#DeviceServiceLevel computation" option in the OPCUA Server Expert configuration. To enable, launch the configuration tool and go to the "communication" settings and check the "Extended rules" .