Issue:
Customer wants to reset the programming to factory default using the keypad of the drive.
Product Line:
ATV340 series
Environment:
All
Cause:
NA
Resolution:
NOTE: It is Always advised to save the current configuration, prior to doing a full factory reset.
Customer wants to reset the programming to factory default using the keypad of the drive.
Product Line:
ATV340 series
Environment:
All
Cause:
NA
Resolution:
Go to Menu 7: Files Management and press enter. Scroll down to 7.2: Factory Settings and press enter.
Scroll down to Parameter group list and press enter, select "All" if a full factory reset is needed. Press ESC to go back.
Scroll down to Go To Factory Settings and press enter. A Warning message will appear, press ENT again to continue.
Factory reset is done.
NOTE: It is Always advised to save the current configuration, prior to doing a full factory reset.
Publikováno pro:Schneider Electric Česká republika

