{}

Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
Jak vám dnes můžeme pomoci?
Why does my CSH2 battery state of charge change with the load turned off, or no load connected?
Issue: Why does my CSH2 battery state of charge change with the load turned off, or no load connected?

Product Line: CSH2 Smart-UPS Charge Mobile Battery for Microsoft Surface Hub 2

Environment: all models, all serial numbers

Cause: If the CSH2 is disconnected from AC input, and the 24V DC output is turned on, the battery will discharge even if there is no load connected to the CSH2, or if the connected Microsoft Surface Hub 2 is turned off. The expected runtime with the CSH2 on 100% state of charge, 24 V DC output on, no load, on battery (AC input disconnected), is 43 hours.

Resolution: To avoid discharging the CSH2 battery while the load is turned off for an extended period, it is recommended to leave the CSH2 connected to AC input, or to turn off the 24 V DC output.

 

Schneider Electric Česká republika

Zjistěte více
Produkt:
Zjistěte více
Produkt:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.