There are only few parameter setting required for enabling dynamic breaking function through braking resistor.
1. The parameter "STC"( stop mode) should be set to "RMP"(ramp stop).
2. The parameter "BRA"(dec ramp adaption) should be set to "NO".
1. The parameter "STC"( stop mode) should be set to "RMP"(ramp stop).
2. The parameter "BRA"(dec ramp adaption) should be set to "NO".