Issue: 
Inrush current of the ATV61 / ATV71 High horse power VFDs.
Product Line:
ATV61HC11N4, ATV61HC31N4, ATV61HC25N4, ATV61HC40N4, ATV61HC63N4
ATV71HD90N4, ATV71HC20N4, ATV71HC25N4, ATV71HC31N4, ATV71HC50N4
Environment:
All
Cause:
Application requirement.
Resolution:
Inrush current
Drive power [kW] I peak [A] (~2ms) I peak [A] (~2ms)
Inrush current of the ATV61 / ATV71 High horse power VFDs.
Product Line:
ATV61HC11N4, ATV61HC31N4, ATV61HC25N4, ATV61HC40N4, ATV61HC63N4
ATV71HD90N4, ATV71HC20N4, ATV71HC25N4, ATV71HC31N4, ATV71HC50N4
Environment:
All
Cause:
Application requirement.
Resolution:
Inrush current
Drive power [kW] I peak [A] (~2ms) I peak [A] (~2ms)
ATV71    ATV61               @ 480V +10%                        @ 400V
 90               110                   275                                        208
 200             250                   556                                        421
 250             315                   764                                        579
 310             400                   802                                        608
 500             630                  1500                                     1136