Can I run a 6 terminal motor either in star/ delta by using VFD ATV61/ 212 ?

Yes, You can run 6 terminal motor in VFD by connecting the motor in Delta connection. You can connect the motor terminals in Delta (U1V2, V1W2, W1U2) and three terminals can be connected to VFD output terminals. The VFD can be programmed and operated like normal induction motor.