This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
What is meant by enhanced discrimination by cascading ?

Enhanced discrimination is the result of the exclusive Compact NSX Roto-active breaking technique which operates as follows: due to the short-circuit current (electrodynamics forces), the contacts in both devices simultaneously separate. The result is major limitation of the short-circuit current

The dissipated energy provokes the reflex tripping of the downstream device, but is insufficient to trip the upstream device

kindly find attached PDF for more clarifications

Schneider Electric Egypt and North East Africa

Attachment(s)
enhanced discrimination through cascading.pdf [160.36 KB]