How to disconnect the capacitor banks in Varset in case of switching on the Generator engine ?

Inside the Varset ,there is an input on terminal blocks 1 and 2 used for disconnecting the banks once the generator is switched on.

It is required to connect a normally closed contact between point 1 and 2,which will be opened when the generator starts and remains closed once generator stops.

The opening of contact between these two points cuts the power on regulator,and consequently disconnect the capacitor banks.