Issue
All changes in Unity PRO will require a synchronization between Unity and the WMY module. Synchronization can be accomplished by using the .stu file and .xvm file. In some case the synchronization using .STU file takes longer and therefore using a .XVM file is more efficient.
Product Line
Factory cast HMI (WMY, NMW)
Resolution
Below the steps on .xvm synchronization:
After rebuilding and saving Unity PRO:
Export “Variable & FB Instances” as .XVM
On Web Designer, “Import PLC Symbols”, import the up-to-date .XVM file to the Device0.
Transfer the up-to-date Web Designer project to the target WMY100 (PC->Target)
When prompted to reboot module, click “Yes”.
All changes in Unity PRO will require a synchronization between Unity and the WMY module. Synchronization can be accomplished by using the .stu file and .xvm file. In some case the synchronization using .STU file takes longer and therefore using a .XVM file is more efficient.
Product Line
Factory cast HMI (WMY, NMW)
Resolution
Below the steps on .xvm synchronization:
After rebuilding and saving Unity PRO:
Export “Variable & FB Instances” as .XVM
On Web Designer, “Import PLC Symbols”, import the up-to-date .XVM file to the Device0.
Transfer the up-to-date Web Designer project to the target WMY100 (PC->Target)
When prompted to reboot module, click “Yes”.
Released for: Schneider Electric Egypt and North East Africa


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.