Issue:
LFF2 fault code on the ATV61 or ATV71 drives
Product Line:
Altivar ATV61 and ATV71
Environment:
All
Cause:
The drive is powering up with a LFF2 fault.
Resolution:
LFF2 LFF3 and LFF4 are all 4 to 20mA loss of follower faults.
Check your programming in the 1.8 Fault Management menu under 4 to 20mA Loss. Turn this function off if you are not using it.
Check your analog signal to see if the drive is getting a 4mA min signal.
LFF2 fault code on the ATV61 or ATV71 drives
Product Line:
Altivar ATV61 and ATV71
Environment:
All
Cause:
The drive is powering up with a LFF2 fault.
Resolution:
LFF2 LFF3 and LFF4 are all 4 to 20mA loss of follower faults.
Check your programming in the 1.8 Fault Management menu under 4 to 20mA Loss. Turn this function off if you are not using it.
Check your analog signal to see if the drive is getting a 4mA min signal.
Released for: Schneider Electric Egypt and North East Africa




Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.