Issue:
Reading the status of local or remote via binary point (BacNet)
Product Line:
Altivar 212
Environment:
All serial numbers for Altivar 212
Cause:
N/A
Resolution:
Under the Binary Value Objects Instance, #4 reads and indicates if the drive is locally controlled or not. It is dependent on several other factors as well.
Please reference the chart below

Reading the status of local or remote via binary point (BacNet)