Issue:
The ATV32 drive has a blank display and will not power up.
Product Line:
ATV32 drives
Environment:
All
Cause:
Power board appears to be inoperative.
Resolution:
If the Display is blank there are some troubleshooting checks to do.
1) Check to see if you have line voltage L1 L2 L3 on the input of the drive.
2) Check the DC bus on PA to PC if it applies. DC bus voltage should be Line voltage times Square root of 2.
3) Check the + 10vdc and +24vdc power supplies.
4) Remove all control wires from the drive to make sure nothing is pulling down the DC voltage supplies.
If the drive is inoperative, you will need to replace the drive.
The ATV32 drive has a blank display and will not power up.
Product Line:
ATV32 drives
Environment:
All
Cause:
Power board appears to be inoperative.
Resolution:
If the Display is blank there are some troubleshooting checks to do.
1) Check to see if you have line voltage L1 L2 L3 on the input of the drive.
2) Check the DC bus on PA to PC if it applies. DC bus voltage should be Line voltage times Square root of 2.
3) Check the + 10vdc and +24vdc power supplies.
4) Remove all control wires from the drive to make sure nothing is pulling down the DC voltage supplies.
If the drive is inoperative, you will need to replace the drive.
Released for: Schneider Electric Egypt and North East Africa


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.