Issue:
This video shows how to reset an Air Filter Run Hours violation alarm on a Uniflair Unit.
Product line:
All Unfair Units with Push-Button Display, All Chilled Water Uniflairs.
Environment:
All Serial Number with Push-Button Units.
Cause:
Repair, Install, Maintenance.
Resolution
To clear Air filters run hour violations from a Uniflair push button display.
Press <> PRG.
Settings Menu <> ENTER.
Code <> 00000 ENTER.
Hour-Meter Settings <> ENTER.
ENTER down to reset hit ENTER change display to OK and then ENTER Again.
Alarm has been cleared. Review the following video for a demonstration of this procedure.