Issue:
ATV61 or ATV71 in MCC configure Hand Off-Auto Selector for Ethernet Control.
Product Line:
Altivar 61 Altivar 71 ATV61 ATV71
Cause:
Configuration
Environment:
Schneider Electric Motor Control Center
Resolution:
Forced Local is programmed from the factory and the IP Address goes away when the Forced Local contact is On.
Program as follows to prevent this;
Command Menu
Ref 1 channel: Com Card (Auto)
Profile: Separate or I/O (*Depends on PLC Assemblies)
(**Note: If you set Profile to I/O, then need to change back, the drive is reset to factory settings)
Cmd Ch1: Com Card
Cmd Ch2:Terminals
Cmd Switching: LI3
Ref 2 Sw: LI3
Ref 2 Ch: AI1 (Hand)
Communications Menu
Forced Local
Forced Local Assignment and Reference - Change to NO
ATV61 or ATV71 in MCC configure Hand Off-Auto Selector for Ethernet Control.
Product Line:
Altivar 61 Altivar 71 ATV61 ATV71
Cause:
Configuration
Environment:
Schneider Electric Motor Control Center
Resolution:
Forced Local is programmed from the factory and the IP Address goes away when the Forced Local contact is On.
Program as follows to prevent this;
Command Menu
Ref 1 channel: Com Card (Auto)
Profile: Separate or I/O (*Depends on PLC Assemblies)
(**Note: If you set Profile to I/O, then need to change back, the drive is reset to factory settings)
Cmd Ch1: Com Card
Cmd Ch2:Terminals
Cmd Switching: LI3
Ref 2 Sw: LI3
Ref 2 Ch: AI1 (Hand)
Communications Menu
Forced Local
Forced Local Assignment and Reference - Change to NO
Released for: Schneider Electric Egypt and North East Africa
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.