Issue:
ATV320: Can you use one 24v dc supply for multiple drives to the STO terminal?
Product Line:
ATV
Environment:
All
Cause:
Wiring
Resolution:
No, to avoid nuisance tripping, you have to have a solid 24v dc to each STO terminal so it is not recommended to use 1- 24v supply to multiple drives.
ATV320: Can you use one 24v dc supply for multiple drives to the STO terminal?
Product Line:
ATV
Environment:
All
Cause:
Wiring
Resolution:
No, to avoid nuisance tripping, you have to have a solid 24v dc to each STO terminal so it is not recommended to use 1- 24v supply to multiple drives.
Released for: Schneider Electric Egypt and North East Africa