Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
This FAQ has been written for NEAL (North East Africa and Levant) region. If you are looking for information for another region, please select the correct country from the top-left dropdown in the page and 'Navigate to Browse FAQs' in the Support menu.
Can we install Earth Fault protection for a Three pole ACB with micrologic 6 or 7 trip unit without external Neutral CT?
There are two types of ground-fault protection:
1- Residual:
The function determines the zero-phase sequence current, i.e. the vector sum of the phase and neutral currents
2- Source Ground Return:
Using a special external sensor, this function directly measures the fault current returning to the transformer via the earth cable.

In case of 3 pole breaker (4-wire system), for ground-fault protection, it is mandatory to install an external CT for calculating the current to ground, thanks to a vectorial sum of phases and neutral currents. While for the 4 pole CB, it is not mandatory to install an external CT.

Schneider Electric Egypt and North East Africa

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings