Issue:
They need to change the function of the output relay from Normally Open contact to a Normally Closed contact.
Product line:
Altivar Process, ATV600 ATV900
Environment:
all
Cause:
The Altivar Process drives come with only R1 having a normally open and normally closed contact. R2, R3 and the extended IO Card relays are all Normally Open only.
Resolution:
Under the Relay configuration menu (i.e. R2 Configuration > go to R2 Active at. The factory setting is 1 (closed). Change this value to 0 for active when open to invert the relay output signal.
NOTE: Operating State Fault (FLT) cannot be assigned to 0. If an additional NC contact is needed for Fault indication, add an external control relay with the additional contacts.
They need to change the function of the output relay from Normally Open contact to a Normally Closed contact.
Product line:
Altivar Process, ATV600 ATV900
Environment:
all
Cause:
The Altivar Process drives come with only R1 having a normally open and normally closed contact. R2, R3 and the extended IO Card relays are all Normally Open only.
Resolution:
Under the Relay configuration menu (i.e. R2 Configuration > go to R2 Active at. The factory setting is 1 (closed). Change this value to 0 for active when open to invert the relay output signal.
NOTE: Operating State Fault (FLT) cannot be assigned to 0. If an additional NC contact is needed for Fault indication, add an external control relay with the additional contacts.
Released for: Schneider Electric Egypt and North East Africa






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Center
Find support resources for all your needs, in one place.